toner
4-3924-01 Carbon Dioxide Gas Stationary Detection Alarm (Gas Buster) For Safety management GB-CO2-L
model:
4-3924-01
category:
toner
Product Description
Product Model: 4-3924-01 Features No construction requi […]
Contact Us
Product Details
Product Model: 4-3924-01
Features
- No construction required, easy to install.
- Calibrated cartridge replacement type.
- It enables solenoid valve control and data log management using alarm contact/analog output.
- Equipped with one-touch air conditioning and alarm test mode.
Spec
- Measuring range (%): 0.04 ~ 5.00
- Type: For safety management
- Number of pieces: 1
- Detection principle: NDIR method
- Detection method: Diffusion method
- Alarm setting values: OFF (AL1)/0.50% (AL2)
- Response time: 40 seconds or less (T 90)
- Alarm operation: 2-step alarm, LED lamp flashing, electronic buzzer
- External output: Relay non-voltage 1 c contact, DC 30 V/1 A
- Analog output: 4 -20 mA
- Size: 167 x 40 x 82 mm
- Power supply: 100 VAC (AC adapter included)
- Operating temperature range: 0 ~ 40 degrees Celsius
- Operating humidity: 15 ~ 85% RH (noncondensing)
- Weight: 250 g
Related product recommendations
You may also be interested in the following products
61-9736-68 Gas Detector Tube 179S Ethylbenzene 11017900
model: 61-9736-68
brand: KITAGAWA, KOMYO RIKAGAKU KOGYO K. K.
1-5529-01 [Discontinued]Pretreatment Agent for Water Quality Measuring Reagent LR-Clo-Ra LR-ClO-RA
model: 1-5529-01
brand: KYORITSU CHEMICAL-CHECK Lab., Corp.
67-8072-91 Mercury Rod Thermometer 0~360 (1.0) L330 General Calibration & Traceability Certificates T-1959-ST2
model: 67-8072-91
brand: TOA KEIKI